MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS
Use a non-combustible floor protector under the unit, extending 3” (76mm) past the side of unit
(or less if installed at closer clearances) and 6” (150mm) in front of Room Heater door.
Alcove Dimensions (Rear Vent Only):
Minimum Height - 42” (1065mm), Minimum Width - 32” (815mm),
Maximum Depth - 24” (610mm)
B
A
B
C
B
B
Free Standing and Alcove (rear only) Installation Clearances:
A 10.5” (267mm) D 6” (150mm)
B 2” (50mm) E 3” (75mm)
C 12” (305mm)
NOTE: Minimum clearances are for temperature concerns and do not allow for enough room
for maintenance. Please allow enough room on the sides for routine maintenance,
6” - 12” (150mm - 305mm) of clearance to non-movable objects (i.e. walls)
is recommended. Also, clearance to the back of the Room Heater is needed for
replacement of the filter.